Optimasi Sistem HVAC di Gedung UMKM 3 Lantai Universitas Sumatera Utara Menggunakan Pipe Flow Expert untuk efisiensi energi dan pengurangan Head Loss
Abstract
Heating, ventilation, and air conditioning (HVAC) systems are essential for ensuring comfort and energy efficiency. Due to high head loss in the HVAC piping system, the three-story SME building faces energy efficiency issues, leading to increased energy consumption and operational costs. Using Pipe Flow Expert software, this study aims to optimize the SME building’s HVAC system to conserve energy. The main goal of this research is to reduce energy consumption and operational costs by decreasing head loss within the piping network and improving pump efficiency. To achieve head loss reduction and decrease system power requirements, this study utilized Pipe Flow Expert simulations to test various piping configurations. Results show that pipes with smaller diameters and longer lengths tend to generate greater head loss, causing pumps to consume more power. Recommendations for modifying pipe diameter and selecting materials with lower roughness coefficients successfully reduced head loss by up to 30%, enabling pumps to operate more efficiently. A total power reduction from 5.96 kW to 4.172 kW was observed. This study concludes that optimizing piping systems and enhancing pump efficiency significantly improves the performance of HVAC systems in the SME building at Universitas Sumatera Utara. Additionally, this study provides a valuable contribution toward developing more efficient and environmentally friendly HVAC systems and can serve as a model for similar research and development in the future.
Full Text:
PDFReferences
H. Seol, D. Arztmann, N. Kim, and A. Balderrama, “Estimation of Natural Ventilation Rates in an Office Roomwith 145 mm-Diameter Circular Openings Using the Occupant-Generated Tracer-Gas Method,” Sustain., vol. 15, no. 13, pp. 1–25, 2023, doi: 10.3390/su15139892.
C. Qin, S. Z. Zhang, Z. T. Li, C. Y. Wen, and W. Z. Lu, “Transmission mitigation of COVID-19: Exhaled contaminants removal and energy saving in densely occupied space by impinging jet ventilation,” Build. Environ., vol. 232, no. October 2022, p. 110066, 2023, doi: 10.1016/j.buildenv.2023.110066.
Z. H. Siregar, J. Jufrizal, and B. K. Putra, “Pengaruh penambahan regenerator terhadap performansi mesin stirling tipe gamma,” J. Mekanova Mek. Inov. dan Teknol., vol. 8, no. 2, p. 194, 2022, doi: 10.35308/jmkn.v8i2.5957.
A. Aflaki, M. Esfandiari, and A. Jarrahi, “Multi-Criteria Evaluation of a Library’s Indoor Environmental Quality in the Tropics,” Buildings, vol. 13, no. 5, 2023, doi: 10.3390/buildings13051233.
L. R. Jia, Q. Y. Li, X. Chen, C. C. Lee, andJ. Han, “Indoor Thermal andVentilation Indicator on University Students’ Overall Comfort,” Buildings, vol. 12, no. 11, pp. 1–18, 2022, doi: 10.3390/buildings12111921.
Y. Chang, Z. Ai, J. Ye, and G. Ma, “A cost-effectiveness assessment of the operational parameters of central HVAC systems during pandemics,” Build. Simul., vol. 16, no. 5, pp. 667–682, 2023, doi: 10.1007/s12273-023-1000-x.
S. Jin, C. Lee, D. Kim, D. Lee, and S. Do, “Indoor Thermal Environment and Energy Characteristics with Varying Cooling System Capacity and Restart Time,” Sustain., vol. 14, no. 15, pp. 1–16, 2022, doi: 10.3390/su14159392.
X. Kong, Y. Chang, M. Fan, and H. Li, “Analysis on the thermal performance of low-temperature radiant floor coupled with intermittent stratum ventilation (LTR-ISV) for space heating,” Energy Build., vol. 278, p. 112623, 2023, doi: 10.1016/j.enbuild.2022.112623.
A. M. Stamatellou, O. Zogou, and A. Stamatelos, “Energy Cost Assessment and Optimization of Post-COVID-19 Building Ventilation Strategies,” Sustain., vol. 15, no. 4,
2023, doi: 10.3390/su15043422.
R. Madani and A. E. Winahyo, “Simulation-Based Exploration with Energyplus asan Energy Efficiency Strategy,” UKaRsT, vol. 8, no. 1, pp. 55–66, 2024, doi: 10.30737/ukarst.v8i1.5534.
F. Ochs, N. Franzoi, G. Dermentzis, W. Monteleone, and M. Magni, “Monitoring and simulation-based optimization of two multi-apartment NZEBs with heat pump, solar thermal and PV,” J. Build. Perform. Simul., vol. 17, no. 1, pp. 1–26, 2024, doi: 10.1080/19401493.2023.2227605.
G. M. Thornton, B. A. Fleck, D. Dandnayak, E. Kroeker, L. Zhong, and L. Hartling, “The impact of heating, ventilation and air conditioning (HVAC) design features on the transmission of viruses, including the 2019 novel coronavirus (COVID-19): A systematic review of humidity,” PLoS One, vol. 17, no. 10 October, pp. 1–23, 2022, doi: 10.1371/journal.pone.0275654.
L. Liu and Y. Huang, “HVAC Design Optimization for Pharmaceutical Facilities with BIM and CFD,” Buildings, vol. 14, no. 6, 2024, doi: 10.3390/buildings14061627.
P. R. Dehankar, D. M. N. N. A. Farooqui, H. Ahmed, A. Khan, J. Hamdulay, and M. Mulla, “Designing of Energy efficient HVAC system,” Int. J. Res. Publ. Rev., vol. 5, no. 5, pp. 4424–4427, 2024, doi: 10.55248/gengpi.5.0524.1243.
M. Yunus, N. Putra, I. I. Hakim, F. Yulia, and Nasruddin, “Multi-Objective Optimization of Techno-Economic Feasibility of Heat Pipe Heat Exchanger (HPHE) for Air Conditioning Systems,” Adv. Sci. Technol., vol. 136, pp. 39–45, 2024, doi: 10.4028/p-k1GC4g.
M. Rakibuzzaman, S. H. Suh, H. W. Roh, K. H. Song, K. C. Song, and L. Zhou, “Hydraulic Performance Optimization of a Submersible Drainage Pump,” Computation, vol. 12, no. 1, pp. 1–16, 2024, doi: 10.3390/computation12010012.
W. L. A, Q. Yang, Y. Yang, L. Ji, W. Shi, and R. Agarwal, “Optimization of pump transient energy characteristics based on response surface optimization model and computational fluid dynamics,” Appl. Energy, vol. 362, no. 15 May 2024, p. 123038, 2024, doi: https://doi.org/10.1016/j.apenergy.2024.123038.
L. Ji et al., “Research Progress of Advanced Design Method, Numerical Simulation, and Experimental Technology of Pumps in Deep-Sea Resource Exploitation,” Water, vol. 16, no. 13, pp. 1–49, 2024, doi: 10.3390/w16131881
DOI: https://doi.org/10.35308/jmkn.v10i2.10689
Refbacks
- There are currently no refbacks.
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.